Merv Rating
MERV 11
Merv Rating
MERV 13
Merv Rating
MERV 14
Nominal Depths
2" & 4"
Rated Face Velocity
250 FPM (2") / 500 FPM (4")
Recommended Final Resistance
1.5" W.G. (Both Depths)
Continous Operating Temparature
750°F (399°C)
Initial Resistance
24x24x2, MERV 11 Efficiency, 1000 CFM = .28 In. W.G.24x24x2, MERV 13 Efficiency, 1000 CFM = .43 In. W.G.24x24x2, MERV 14 Efficiency, 1000 CFM = .46 In. W.G.24x24x4, MERV 11 Efficiency, 2000 CFM = .40 In. W.G.24x24x4, MERV 13 Efficiency, 2000 CFM = .55 In. W.G.24x24x4, MERV 14 Efficiency, 2000 CFM = .65 In. W.G.
Rated Air Flow Capacity (CFM)
24x24x2 = 1000 CFM (All efficiencies)24x24x4 = 2000 CFM (All efficiencies)
Merv Rating
Both the 2" & 4" variants are available in MERV 11, MERV 13 & MERV 14 efficiencies
Construction
Box Style w/24 gauge aluminized steel sidesCorrugated aluminum separatorsExpanded metal grid (both sides)
Classifications
UL 900 for flammability
Media
High Efficiency, Microglass Paper