About this item

Parker LoadTECH 12-inch MERV 11 rigid cell filters use white, 100% synthetic E-Pleat media for heating, ventilating and air conditioning systems. Preformed media channels guide airflow through the filter for even loading and full media utilization. Adhesive beads bond the pleats into a rigid pack. The approved 12-inch bulletin identifies these filters for variable air volume systems and applications including offices, schools, data centers and industrial manufacturing.

The water-resistant media withstands humidity and exposure to sensible moisture, with the specification noting that moisture may temporarily increase resistance. The synthetic sheet resists tearing and abrasion. Parker links high dust-holding capacity with longer filter life and fewer changeouts, and low pressure drop with reduced energy use; actual results depend on the application.

The high-impact polystyrene frame is resistant to moisture, chemicals and corrosion, and mechanically locks together at each corner. Foamed hot-melt adhesive seals the media pack into the cell sides to prevent bypass between the pack and frame. Standard configurations are available in box and single-header construction.

  • MERV 11; box and single-header configurations.
  • Nominal depth: 12 inches; actual depth: 11-1/2 inches.
  • Standard initial resistance at rated airflow: box 0.17 in. w.g.; single header 0.19 in. w.g.
  • Rated face velocity: 500 FPM; recommended final resistance: 1.50 in. w.g.
  • Standard continuous operating temperature: 170°F (77°C).
  • Classified per UL 900 for flammability.
  • Standard single-header configuration: 3/4 x 3/4 inch header on the air-entering side.
71794_LoadTech_Filters_MERV11_12in_LoadTECH_PLT12_M11_bulletin
71794_LoadTech_Filters_MERV11_12in_LoadTECH_PLT12_M11_bulletin.pdf
Merv Rating MERV 11
Nominal Depths 12"
Rated Face Velocity 500 FPM
Recommended Final Resistance 1.50" W.G. (Box & Single Header)
Continous Operating Temparature 170°F (77°C)
Initial Resistance
  • 24x24x12 (Box) @ 2000 CFM = .17" W.G.
  • 24x24x12 (Single Header) @ 2000 CFM = .19" W.G.
  • Rated Air Flow Capacity (CFM) 24x24x12 = 2000 CFM (Box or Single Header)
    Merv Rating MERV 11
    Construction
  • Box and single header styles are available
  • High-impact polystyrene (HIPS) frame
  • Fully incinerable
  • Classifications UL 900 for flammability
    Media
  • Proprietary E-Pleat synthetic media
  • Enhanced dust holding capacity