My Cart $-.--
Quick Order
0
Home HVAC & Paint Process Rigid Cell Parker LoadTECH 12" Depth MERV 15/15A Box & Single Header Extended Rigid Cell Filter with E-Pleat® Media

Parker LoadTECH 12" Depth MERV 15/15A Box & Single Header Extended Rigid Cell Filter with E-Pleat® Media

PART PLT12-M15
SUPPLIER ---
SUPPLIER PART # ---
-- Select -- MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15
-- Select -- Box Single Header Box Single Header Box Single Header Box Single Header
-- Select -- 12x24x12 12x24x12 24x24x12 24x24x12 20x20x12 20x20x12 20x24x12 20x24x12
Calculating price...
QUANTITY

About this item

Parker LoadTECH 12-inch MERV 15/15A extended rigid cell filters use E-Pleat® media technology for HVAC filtration in hospitals, healthcare facilities, schools, universities and clean manufacturing facilities. The gold-tinted, 100% synthetic media has an embossed, two-layer gradient-density structure. Preformed channels guide air through the filter for even loading and full use of the media. Parker identifies this family for variable air volume systems.

Adhesive beads bond the pleats into a rigid pack. The high-impact polystyrene frame resists moisture, chemicals and corrosion, while foamed hot-melt adhesive seals the media pack to the frame to prevent bypass at that joint. The media resists tearing and abrasion; exposure to humidity or moisture may temporarily increase resistance. Low pressure drop supports reduced energy use, and high dust-holding capacity supports longer filter life and fewer changeouts.

The family includes box/no-header and single-header configurations in four nominal sizes. Single-header models have a 3/4 x 3/4-inch header on the air-entering side. Gaskets are optional, and special sizes are not available.

  • Nominal sizes: 12 x 24 x 12, 20 x 20 x 12, 20 x 24 x 12 and 24 x 24 x 12 in.
  • Rated airflow for standard models: 1,000-2,000 CFM, depending on size.
  • Initial resistance at rated airflow: 0.29 in. W.G. for standard box models; 0.39 in. W.G. for standard single-header models.
  • Media area: 73-146 sq. ft. for standard box models; 59-126 sq. ft. for standard single-header models.
  • MERV 15 and MERV-A 15 per ASHRAE 52.2-2017 with Appendix J; performance testing at 492 FPM on a 24 x 24-inch face size.
  • Rated face velocity: 500 FPM; recommended final resistance: 1.50 in. W.G.
  • Continuous operating temperature: up to 170 degrees F.
  • Classified per UL 900 for flammability.
71827_HVAC_12_LoadTech_MERV_15_15A
71827_HVAC_12_LoadTech_MERV_15_15A.pdf
Nominal Depth 12"
Rated Face Velocity 500 FPM
Recommended Final Resistance 1.50" W.G. (Box & Single Header)
Continuous Operating Temperature 170°F (77°C)
Initial Resistance
  • 24x24x12 (Box) @ 2000 CFM = .29" W.G.
  • 24x24x12 (Single Header) @ 2000 CFM = .39" W.G.
  • Rated Airflow Capacity 24x24x12 = 2000 CFM (Box or Single Header)
    MERV Rating 15/15A
    Construction
  • Box and single header styles are available
  • High-impact polystyrene (HIPS) frame
  • Fully incinerable
  • Classifications UL 900 for flammability
    Media
  • Proprietary E-Pleat synthetic media
  • Enhanced dust holding capacity