Home HVAC & Paint Process Rigid Cell E-Pleat Parker LoadTECH 4" Depth MERV 14 Box & Single Header Extended Rigid Cell Filter with E-Pleat Media

Parker LoadTECH 4" Depth MERV 14 Box & Single Header Extended Rigid Cell Filter with E-Pleat Media

PART PLT4-M14
SUPPLIER ---
SUPPLIER PART # ---
-- Select -- MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14
-- Select -- Box Single Header Box Single Header Box Single Header Box Single Header Box Single Header Box Single Header Box Single Header
-- Select -- 12x24x4 12x24x4 24x24x4 24x24x4 16x20x4 16x20x4 16x25x4 16x25x4 20x25x4 20x25x4 20x20x4 20x20x4 20x24x4 20x24x4
Calculating price...
QUANTITY

About this item

Parker LoadTECH 4-inch MERV 14 extended rigid cell filters use E-Pleat media technology for commercial and industrial HVAC systems, including variable air volume systems. The gold-tinted, 100% synthetic media has an embossed, two-layer gradient-density structure. Preformed channels guide air through the filter for even dust loading and full use of the media. Parker lists offices, schools, hospitals, data centers, food processing and manufacturing facilities among the applications for this family.

Adhesive beads bond the pleats into a rigid pack, and a high-impact polystyrene frame resists moisture, chemicals and corrosion. Foamed hot-melt adhesive seals the media pack to the frame to prevent bypass at that joint. The compact 4-inch design simplifies handling and reduces storage space requirements. Low pressure drop supports reduced energy use, while high dust-holding capacity supports longer filter life and fewer changeouts.

The family includes box/no-header and single-header configurations. Single-header models have a 3/4 x 3/4-inch header on the air-entering side. Gaskets are optional, and special sizes are not available.

  • Standard nominal sizes: 12 x 24 x 4, 16 x 20 x 4, 16 x 25 x 4, 20 x 20 x 4, 20 x 24 x 4, 20 x 25 x 4 and 24 x 24 x 4 in.
  • Rated airflow for standard models: 1,000-2,000 CFM, depending on size.
  • Initial resistance at rated airflow: 0.45 in. W.G. for standard box models; 0.51 in. W.G. for standard single-header models.
  • Media area for standard box models: 26-53 sq. ft., depending on size.
  • Standard 16 x 25 x 4 and 20 x 25 x 4 box models have reverse pleat direction.
  • MERV 14 per ASHRAE 52.2-2017; performance testing at 492 FPM on a 24 x 24-inch face size.
  • Rated face velocity: 500 FPM; recommended final resistance: 1.50 in. W.G.
  • Continuous operating temperature: up to 170 degrees F.
  • Classified per UL 900 for flammability.
71864_LoadTech_4in_MERV_14_Bulletin_LoadTECH_Bulletin
71864_LoadTech_4in_MERV_14_Bulletin_LoadTECH_Bulletin.pdf
Nominal Depths 4"
Rated Face Velocity 500 FPM
Recommended Final Resistance 1.50" W.G.
Continous Operating Temparature 170°F (77°C)
Initial Resistance
  • 24x24x4 (Box) @ 2000 CFM = .45" W.G.
  • 24x24x4 (Single Header) @ 2000 CFM = .51" W.G.
  • Rated Air Flow Capacity (CFM) 24x24x4 = 2000 CFM (Box or Single Header)
    Merv Rating MERV 14
    Construction
  • Box and single header styles are available
  • High-impact polystyrene (HIPS) frame
  • Fully incinerable
  • Classifications UL 900 for flammability
    Media
  • Proprietary E-Pleat synthetic media
  • Enhanced dust holding capacity