My Cart $-.--
Quick Order
0
Home HVAC & Paint Process Rigid Cell Parker LoadTECH 4" Depth MERV 15/15A Box & Single Header Extended Rigid Cell Filter with E-Pleat Media

Parker LoadTECH 4" Depth MERV 15/15A Box & Single Header Extended Rigid Cell Filter with E-Pleat Media

PART PLT4-M15
SUPPLIER ---
SUPPLIER PART # ---
-- Select -- MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15 MERV 15
-- Select -- Box Single Header Box Single Header Box Single Header Box Single Header Box Single Header Box Single Header Box Single Header
-- Select -- 12x24x4 12x24x4 24x24x4 24x24x4 16x20x4 16x20x4 16x25x4 16x25x4 20x25x4 20x25x4 20x20x4 20x20x4 20x24x4 20x24x4
Calculating price...
QUANTITY

About this item

Parker LoadTECH 4-inch MERV 15/15A extended rigid cell filters use E-Pleat media technology for commercial and industrial HVAC systems, including variable air volume systems. The gold-tinted, 100% synthetic media has an embossed, two-layer gradient-density structure. Preformed channels guide air through the filter for even dust loading and full use of the media. Parker lists schools, universities, hospitals, healthcare facilities and clean manufacturing facilities among the applications for this family.

Adhesive beads bond the pleats into a rigid pack, and a high-impact polystyrene frame resists moisture, chemicals and corrosion. Foamed hot-melt adhesive seals the media pack to the frame to prevent bypass at that joint. The frame corners mechanically lock together. Low pressure drop supports reduced energy use, while high dust-holding capacity supports longer filter life and fewer changeouts.

The family includes box/no-header and single-header configurations. Single-header models have a 3/4 x 3/4-inch header on the air-entering side. Gaskets are optional, and special sizes are not available.

  • Standard nominal sizes: 12 x 24 x 4, 16 x 20 x 4, 16 x 25 x 4, 20 x 20 x 4, 20 x 24 x 4, 20 x 25 x 4 and 24 x 24 x 4 in.
  • Rated airflow for standard models: 1,000-2,000 CFM, depending on size.
  • Initial resistance at rated airflow: 0.53 in. W.G. for standard box models; 0.66 in. W.G. for standard single-header models.
  • Media area: 32-63 sq. ft. for standard box models; 24-55 sq. ft. for standard single-header models.
  • MERV 15 and MERV-A 15 per ASHRAE 52.2-2017 with Appendix J; performance testing at 492 FPM on a 24 x 24-inch face size.
  • Rated face velocity: 500 FPM; recommended final resistance: 1.50 in. W.G.
  • Continuous operating temperature: up to 170 degrees F.
  • Classified per UL 900 for flammability.
71866_HVAC_4_LoadTech_MERV_15_4in_Bulletin
71866_HVAC_4_LoadTech_MERV_15_4in_Bulletin.pdf
Nominal Depths 4"
Rated Face Velocity 500 FPM
Recommended Final Resistance 1.50" W.G.
Continous Operating Temparature 170°F (77°C)
Initial Resistance
  • 24x24x4 (Box) @ 2000 CFM = .53" W.G.
  • 24x24x4 (Single Header) @ 2000 CFM = .66" W.G.
  • Rated Air Flow Capacity (CFM) 24x24x4 = 2000 CFM (Box or Single Header)
    Merv Rating MERV 15/15A
    Construction
  • Box and single header styles are available
  • High-impact polystyrene (HIPS) frame
  • Fully incinerable
  • Classifications UL 900 for flammability
    Media
  • Proprietary E-Pleat synthetic media
  • Enhanced dust holding capacity