Home HVAC & Paint Process Rigid Cell Rigid Cell Air Filters Parker Airguard Variflow VMC MERV 11, 13, and 14 High Efficiency Extended Surface Rigid Cell Filter (Double Header Only)

Parker Airguard Variflow VMC MERV 11, 13, and 14 High Efficiency Extended Surface Rigid Cell Filter (Double Header Only)

PART VMC
SUPPLIER ---
SUPPLIER PART # ---
-- Select -- MERV 11 MERV 11 MERV 11 MERV 11 MERV 11 MERV 13 MERV 13 MERV 13 MERV 13 MERV 13 MERV 13 MERV 13 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14 MERV 14
-- Select -- 60-65 60-65 60-65 60-65 60-65 80-85 80-85 80-85 80-85 80-85 80-85 80-85 90-95 90-95 90-95 90-95 90-95 90-95 90-95 90-95 90-95
-- Select -- 12x24x12 24x24x12 24x24x12 20x20x12 20x20x6 24x24x6 12x24x12 24x24x12 16x20x12 20x25x12 20x20x12 20x24x12 24x24x6 12x24x12 24x24x12 24x24x12 24x24x12 16x20x12 18x24x12 20x20x12 20x24x12
-- Select -- None None Upstream None None None None None None None None None None None None Downstream Upstream None None None None
Calculating price...
QUANTITY

About this item

The Parker Airguard Variflow® Series are rigid-cell extended surface filters engineered for commercial and industrial HVAC systems requiring consistent efficiency and structural integrity under demanding conditions. Available in MERV 11, 13, and 14 efficiencies, Variflow filters use microglass paper media and corrugated aluminum separators to maintain low pressure drop and uniform airflow.

Constructed for durability, the Variflow family includes multiple configurations—such as the VMC model, featuring a double-header, all-metal construction ideal for high-temperature or high-humidity environments. Designed to perform in variable air volume (VAV) systems, these filters are rated for temperatures up to 500°F (260°C) and deliver energy-efficient, long-lasting air filtration for commercial buildings, healthcare facilities, and industrial plants.

  • Available in MERV 11, 13, and 14 efficiencies
  • Nominal depths of 6" and 12" for flexible installation
  • Rated for 250 to 500 FPM face velocity
  • Handles airflow capacities from 500 to 2000 CFM
  • Rigid cell construction ensures durability in turbulent or variable volume systems
  • Water-resistant microglass paper media with antimicrobial option
  • Operating temperature limits: 350°F (metal construction)
72014_Airguard_VARIFLOW_A_VFLOW
72014_Airguard_VARIFLOW_A_VFLOW.pdf
Merv Rating MERV 11
Merv Rating MERV 13
Merv Rating MERV 14
Nominal Depths 6", 12"
Rated Face Velocity 6" 250, 12" 500 FPM
Initial Resistance
  • 24x24x12 (MERV 14) = .65" W.G.
  • 24x24x12 (MERV 13) = .60" W.G.
  • 24x24x12 (MERV 11) = .43" W.G.
  • 24x24x6 (MERV 14) = .38" W.G.
  • 24x24x6 (MERV 13) = .35" W.G.
  • 24x24x6 (MERV 11) = .20" W.G.
  • Recommended Final Resistance 1.5" W.G.
    Continous Operating Temparature 350°F
    Media Area
  • 24x24x12 = 124 Square Feet
  • 24x24x6 = 56 Square Feet
  • Rated Air Flow
  • 24x24x12 = 2000 CFM
  • 24x24x6 = 1000 CFM
  • Merv Rating 11, 13, 14
    Media Ultrafine Microglass Paper Media
    Style Rigid Cell Filter – Double Header